Reinforcement Structure
- Water Tank Panel
- Watertightness, Drain Capability and Strength of Water Tank
- Reinforcement Structure
- Partition Type Water Tank
1. Inner Reinforced GRP Water Tank
Internally Reinforced System
- - It is possible that various capacity’s design and flexible space should be used by GRP panels standardized
- - Excellent water tightness, hygienic conditions and non-leakage applied internally reinforced stay(Stainless)
-
NO. Name Material 1 Manhole Panel GRP 2 External Ladder SS400(HDG) 3 Internal Ladder< /td> GRP 4 Internal Tie Rod STS(PET Coating), STS 304, 316 5 Internal Bracket STS(Epoxy Coating),STS 304, 316 6 Flange Bar, Flat Bar SS400(HDG) 7 External Bracket 8 Corner Bracket 9 Bottom Bracket 10 Corner Frame
-
NO. Name Material 11 Roof Support Pipe GRP(Pultrusion) 12 Base Frame SS400(HDG) 13 Bolts and Nuts Inside STS : Bolt/Nut(304, 316), Washer(316) Roof Panel: acetyl cap bolt(M10) Outside : HDG Bolt + PVC Bolt cap Connection: HDG + Acetyl Cap (M14) Size: M10, M14 14 Sealing Tape PVC Sealant + Butyl or EVA Sealant + PVC Sealant 15 Water Level Gauge Aluminum Case+PE Clear Tube+Socket 16 Name Plate Aluminum(Water Tank Safety Management Instructions)
Strength & Durability of GRP Water Tank
Section | Design Standard |
---|---|
Hydrostatic Pressure | Water pressure reinforcement 4 times standard Transformation rate in filled u with water: Less than 1% form water tank heigh |
Wind Force | Less than 60m/sec |
Earthquake Force | Stable and safe till magnitude 5.0 (Over magnitude 5.0, it needs additional reinforcement) |
Snow load | 60Kg/㎡, , Snow fall less than 30cm |
Illumination Rate | Less than 0.1% |
Out-fitForce | No leakage under condition of vertical 100Kg after install of 100A fitting with 70mm span supprot |
Water Temperature | Usable temperature: Less than 30℃, Limited temperature: Max 70℃ |
Water quality | Tap water, well water: chlorine below 50mg/ℓ Seawater: applicantion Externally Reinforced water tank(max 3m height) |
Features of Internally Reinforced System
-
Excellent Hygienic Conditions
- - Internal tie-rod of water tank is coated with PE and internal bracket is coated with powder.
- - Internal Bolt for tie-rod and bracket is coated with epoxy after fastening.
- - Prevented rust appearance as Chlorine GAS stay through external assembly bolts(HDG) added PVC bolt-caps of water tank.
-
Outstanding View
- - Prevented white peril or rust appearance through external assembly bolts added bolt-capsofWaterTank, and outstanding view.
-
Easy to Assembly
- - Easy to assembly through internal and external optimized options of reinforced system.
-
Best Structure Stability
- - SUNGIL CO., LTD's internally Reinforced System is verified structure stability of water tanks which have built in domestic and international sites for 20years.
2. External Reinforced GRP Water Tank
Externally Reinforced System
- By using external reinforcement bar at the exterior, it is minimizing internal reinforcement bar. Strengthened GRP water tank system is to simplify construction and reinforce cleanliness.
-
NO. Name Material 1 Manhole Panel GRP 2 External Ladder SS400(HDG) 3 Internal Ladder GRP 4 Internal Bracket STS(Powder coating), STS304, 316 5 External Support Tie-rod SS400 + Urethane Coating 6 External Pair Frame/td> SS400(HDG) 7 Corner Bracket 8 Corner Frame 9 Roof support pipe GRP(Pultrusion)
-
NO. Name Material 10 Base Frame SS400(HDG) 11 Bolts and Nuts Inside STS : Bolt/Nut(304, 316), Washer(316) Roof Panel: acetyl cap bolt(M10) Outside : HDG Bolt + PVC Bolt cap Connection: HDG + Acetyl Cap (M14) Size: M10, 14 12 Sealing Tape PVC Sealant + Butyl or EVA Sealant + PVC Sealant 13 Water Level Gauge Aluminum Case+PE Clear Tube+Socket 14 Name Plate Aluminum(Water Tank Safety Management Instructions)
Externally Reinforced System Structural Analysis
FEM - Water Tank Height (3MH-75m)
FEM - External Pair Frame (3MH-75m)
Result of Skid base strength review (Safety Factor 2.0)
Height | Contents | Bending Stress(kg/㎠) | Result | Remark | |
---|---|---|---|---|---|
3.0mH | Main Skid Base | Long term | 1520 < 1600(Allowed value) | OK | |
Short term | 2130 < 2400(Allowed value) | OK |